Hubei Dayu Hanguang Vacuum Electric Co.,Ltd.
CN EN

Vacuum interrupter for load breaking switch TF314L

Model:VITF12/630-20

Category:VI for load breaking switches


Product details

1435823369190371.jpg
Main Technical Parameter
Rated voltage 12KV
Rated current 630A
Rated frequency 50Hz
Rated short-time Power frequency withstand voltage 42kV
Rated lightning impulse withstand voltage 75kV
Rated short-time withstand current 20kA
Rated duration of short-circuit 4 s
Rated peak withstand current 50kA
Rated short-circuit making current(peak) 50kA
Rated active load breaking current 630A
Rated closed-loop breaking current 630A
Rated cable-charging breaking current 10A
Rated breaking current of single capacitor bank 400A
Mechanical endurance 10000 times
Closing force due to bellow and atmosphere 80±30N
Force required to hold contacts open at full storke 140±40N
Circuit resistance at lowest rated contact force ≤45μΩ
Storage life 20 years
Contacts limit erosion 3mm
Weight of movable parts ≤0.7kg
MECHANICAL DATA REQUIRED FOR THE MATCHED VACUUM SWITCHGEAR
Clearance between open contacts 9±1 mm
Contact connection stroke 3±0.5mm
Average opening speed 1.0±0.2m/s
Average closing speed 0.6±0.2m/s
Rated added extemal contact final force 900±50N
Contact bouncing duration at closing operation ≤2 ms
Closing and opening non-simultaneity of three-phase contacts ≤2 ms
Maximum rebound durning opening ≤1.5 mm

Relevant information

Baidu
map