Hubei Dayu Hanguang Vacuum Electric Co.,Ltd.
CN EN

Vacuum interrupter for indoor circuit breaker TD524H

Model:VITD40.5/2000-31.5

Category:VI for indoor circuit breakers

Product details

1.jpg
Main Technical Parameter
Rated voltage 40.5KV
Rated current 2000A
Rated frequency 50Hz
Rated short-time Power frequency withstand voltage 95kV
Rated lightning impulse withstand voltage 185kV
Rated short-circuit breaking current 31.5kA
Rated short-circuit making current(peak) 80kA
Breaking operations of rated short circuit breaking current 30 times
Rated breaking current of single capacitor bank 630A
Rated short-time withstand current 31.5kA
Rated peak withstand current 80kA
Rated duration of short-circuit 4 s
Mechanical endurance 10000 times
Closing force due to bellow and atmosphere 250±50N
Force required to hold contacts open at full storke 330±60N
Circuit resistance at lowest rated contact force ≤20μΩ
Storage life 20 years
Contacts limit erosion 3mm
Weight of movable parts ≤4kg
MECHANICAL DATA REQUIRED FOR THE MATCHED VACUUM SWITCHGEAR
Clearance between open contacts 22±2 mm
Contact connection stroke 3.5±0.5mm
Average opening speed(average of 75% contact gap) 1.8±0.25m/s
Average closing speed(average of last 30% contact gap) 0.8±0.15m/s
Rated added extemal contact final force 4000±200N
Contact bouncing duration at closing operation ≤3 ms
Closing and opening non-simultaneity of three-phase contacts ≤2 ms

Relevant information

Baidu
map