Hubei Dayu Hanguang Vacuum Electric Co.,Ltd.
CN EN

Vacuum interrupter for outdoor circuit breaker TD313B

Model:VITD12/1250-20

Category:VI for outdoor circuit breakers

Product details

1435902044967510.jpg
Main Technical Parameter
Rated voltage 12kV
Rated current 630/1250A
Rated frequency 50Hz
Rated short-time Power frequency withstand voltage 42kV
Rated lightning impulse withstand voltage 75kV
Rated short-circuit breaking current 25kA
Rated short-circuit making current(peak) 63kA
Breaking operations of rated short circuit breaking current 30 times
Rated breaking current of single capacitor bank 400A
Rated short-time withstand current 25kA
Rated peak withstand current 63kA
Rated duration of short-circuit 4 s
Mechanical endurance 10000 times
Closing force due to bellow and atmosphere 70±40N
Force required to hold contacts open at full storke 120±50N
Circuit resistance at lowest rated contact force ≤30μΩ
Storage life 20 years
Contacts limit erosion 3mm
Weight of movable parts ≤0.7 kg
MECHANICAL DATA REQUIRED FOR THE MATCHED VACUUM SWITCHGEAR
Clearance between open contacts 9±1 mm
Contact connection stroke 3.5±0.5mm
Average opening speed(average of 75% contact gap) 1.0±0.25m/s
Average closing speed(average of last 30% contact gap) 0.65±0.15m/s
Rated added extemal contact final force 1600±100N
Contact bouncing duration at closing operation ≤2 ms
Closing and opening non-simultaneity of three-phase contacts ≤1 ms

Relevant information

Baidu